10. Wait for a time corresponding to
tDelayToAlarm1
from the appearance of
WARNING1 signal. Make sure that the ALARM1 signal appears.
11. Note the time taken for the appearance of ALARM1 signal from the appearance of
WARNING1 signal, and compare it with set value (
tDelayToAlarm1
).
12. Wait for a time corresponding to
tDelayToAlarm2
from the appearance of
WARNING2 signal, and make sure that the ALARM2 signal appears.
13. Note the time taken for the appearance of ALARM2 signal from the appearance of
WARNING2 signal, and compare it with set value (
tDelayToAlarm2
).
14. Activate the BLKWRN binary input. The WARNING1 and WARNING2 signals
should disappear.
15. Activate the BLKALM binary input. The ALARM1 and ALARM2 signals should
disappear.
16. Reset the BLKWRN and BLKALM binary inputs. Once again warning and alarm
signals should appear.
17. Reduce the three-phase currents suddenly to value lower than the rated current and
take note of hot spot temperature.
18. Check the warnings reset limit (
HystAbsHPT
). Monitor the WARNING1 and
WARNING2 signals until they disappears on the corresponding binary outputs.
Take the HPTMPMAX readings and compare with the reset level settings.
Verifying LOLINDAY and LOLINYRS outputs
1.
Connect the test set for injection of three-phase currents to the appropriate current
terminals of the IED.
2.
Make sure that the settings in the IED are appropriate, especially set the
EnaAgeCalc
setting as Enable,
TimeToUpdate
setting as
1 hour
and
AgeingRateMeth
setting as
IEC
.
3.
Activate the TOTVALID input and set some temperature value in TOTEMP input.
4.
Supply the IED with three-phase currents slightly more than the rated value.
5.
Note the hot spot temperature (HPTMPMAX) and maintain it for another 1 hour.
6.
Check the LOLINDAY and LOLINYRS outputs after 1 hour and compare it with the
calculated loss of life value using IEC standard method.
11.13.6.2
Completing the test
Continue to test another function or end the test by changing the
Test mode
setting to
Disabled
. Restore connections and settings to their original values, if they were changed
for testing purposes.
Section 11
1MRK 504 165-UUS -
Testing functionality by secondary injection
280
Transformer protection RET670 2.2 ANSI
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...