9.
Check the inverse time delay by injecting a voltage corresponding to 0.8 ×
Vpickup<.
For example, if the inverse time curve A is selected, the trip signals
TRST1 and TRIP trip after a time corresponding to the equation:
( )
1
1
TD
t s
V
Vpickup
=
æ
ö
-
ç
÷
<
è
ø
ANSIEQUATION2428 V1 EN
(Equation 98)
where:
t(s)
Trip time in seconds
TD1
Settable time multiplier of the function for step 1
V
Measured voltage
Vpickup< Set pickup voltage for step 1
For example, if the measured voltage jumps from the rated value to 0.8 times the set
pickup voltage level and time multiplier TD1 is set to 0.05 s (default value), then the
TRST1 and TRIP signals trip at a time equal to 0.250 s ± tolerance.
10. The test above can be repeated to check the inverse time characteristic at different
voltage levels.
11. Repeat the above described steps for Step 2 of the function.
Extended testing
The tests above can be repeated for
2 out of 3
and for
3 out of 3
operation mode.
11.6.1.2
Completing the test
Continue to test another function or end the test by changing the
TESTMODE
setting to
Disabled
. Restore connections and settings to their original values, if they were changed
for testing purposes.
11.6.2
Two step overvoltage protection OV2PTOV (59)
Prepare the IED for verification of settings outlined in Section
.
11.6.2.1
Verifying the settings
1MRK 504 165-UUS -
Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI
213
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...