Figure 47:
Example characteristic
Non-directional ground fault current protection
Procedure
1.
Measure that the trip current is equal to the
INNonDirPU
setting.
The function activates the PICKUP and PUDIRIN output.
2.
Measure the trip time of the timer by injecting a current of 200% of the trip value.
3.
Compare the result with the expected value.
The expected value depends on whether definite time
tINNonDir
or inverse time was
selected.
4.
Continue to test another function or complete the test by setting the test mode to
Disabled
.
Residual overvoltage release and protection
Procedure
1.
Measure that the trip voltage is equal to the
VN_PU
setting.
The function activates the PICKUP and PUVN signals.
2.
Measure the trip time by injecting a voltage 1.2 times set
VN_PU
trip value.
3.
Compare the result with the set
tVN
trip value.