IEC140000144 V1 EN
Figure 16:
Captured synchrophasor data
9.5.2
Verifying the IEEE C37.118/1344 UDP communication
After setting both PMU configuration and the UDP client configuration (As explained in
sections
Setting the PMU station communication (PMU Report)
communication (PMU configuration)
Setting the TCP/UDP client communication
and making sure that the Ethernet communication is set up, click
Connect
on the PMU
Connection Tester tool.
1MRK 504 165-UUS -
Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
Transformer protection RET670 2.2 ANSI
85
Commissioning manual