9.4
Setting the TCP/UDP client communication
As an example of a TCP/UDP client, the openPDC tool (PMU Connection Tester Ver.
4.2.12) from Grid Protection Alliance is used in this section. Install PMU Connection
Tester tool on a PC with Ethernet network adaptor available. The same PC used for
PCM600 can be used to install the PMU Connection Tester tool.
IEC140000133-1-en.vsd
IEC140000133 V1 EN
Figure 9:
PMU Connection Tester tool
The following steps explain how to set the PMU Connection Tester parameters in order to
establish an IEEE C37.118 connection with the PMU:
1.
Set the IP stack on PMU Connection Tester to
IPv4
. Note that the default IP stack
on PMU Connection Tester tool is IPv6.
1MRK 504 165-UUS -
Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
Transformer protection RET670 2.2 ANSI
75
Commissioning manual