1.
Set
AutoInitMode
to
DLD disabled
and
Mode
to
Impedance
.
2.
Activate the switch onto fault
BC
input.
During normal operating conditions, the
BC
input is de-energized.
3.
Apply a three-phase fault condition corresponding to a fault at approximately 45%
of the line or with impedance at 50% of the used zone setting and current greater than
30% of
IBase
.
The
ZACC
input is activated.
4.
Check that the
TRIP
output, external signals and indication are obtained.
11.4.13.2
Initiating ZCVPSOF automatically and setting mode to impedance
1.
Set
AutoInitMode
to
Voltage
and
Mode
to
Impedance
.
2.
Deactivate the switch onto fault
BC
input.
3.
Set the current and voltage inputs to lower than
IphPickup
and
UVPickup
for at least
one second.
4.
Apply a three-phase fault condition corresponding to a fault at approximately 45%
of the line or with impedance at 50% of the used zone setting and current greater than
30% of
IBase
.Apply a two-phase fault condition corresponding to a fault at
approximately 45% of the line or with impedance at 50% of the used zone setting and
current greater than 30% of
IBase
.
The
ZACC
input is activated.
5.
Check that the correct
TRIP
output, external signals and indication are obtained.
11.4.13.3
Initiating ZCVPSOF automatically and setting mode to VILevel
1.
Set
AutoInitMode
to
Voltage
and
Mode
to
VILevel
.
2.
Deactivate the switch onto fault
BC
input.
3.
Set the current and voltage inputs to lower than
IphPickup
and
UVPickup
for at least
one second.
4.
Apply the three-phase currents in such a way that the magnitudes are greater than
IphPickup
and the three-phase voltages in such a way that the magnitudes and lower
than
UVPickup
at least for the duration of the
tDuration
setting.
5.
Check that the correct
TRIP
output, external signals and indication are obtained.
11.4.13.4
Completing the test
Continue to test another function or end the test by changing the
TESTMODE
setting to
Disabled
. Restore connections and settings to their original values, if they were changed
for testing purposes.
1MRK 504 165-UUS -
Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI
171
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...