_
Vdi Ci Icc i Xi
=
×
×
EQUATION2089-ANSI V1 EN
(Equation 112)
The voltage regulation algorithm then increases (for transformer
T2
) or decreases
(for transformer
T1
) the measured voltage by Vdi and compares Vi against the
voltage deadband limits V1 and V2 for the purposes of voltage regulation.
Vi VB Vdi
=
+
EQUATION2091-ANSI V1 EN
(Equation 113)
9.
To cause a tap change, the calculated value for circulating current voltage
adjustment must offset the injected quantity for bus voltage V
B
so that Vi is outside
the voltage deadband created by setting
VDeadband
. Expressed by equation
2
Vdi V
VB
>
-
EQUATION2093-ANSI V1 EN
(Equation 114)
VB Vset
=
EQUATION2095-ANSI V1 EN
(Equation 115)
(for the purposes of this test procedure)
Therfore:
_
2
Ci Icc i Xi V
Vset
×
×
>
-
EQUATION2097-ANSI V1 EN
(Equation 116)
(
)
(
)
2
_
V
Vset
Icc i
Ci Xi
-
>
×
EQUATION2099-ANSI V1 EN
(Equation 117)
10. Using the settings for
VSet
,
VDeadband
, C (Compensating factor) and
Xr2
(transformer short circuit impedance) calculate the magnitude of Icc
_i
necessary to
cause a tap change command.
11. Inject current equal to
I2Base
for Transformer 1 and (
I2Base
- |Icc_
i
|) for
Transformer 2 so that the magnitude of calculated circulating current will cause a
raise command to be issued for Transformer 2 and a lower command for
Transformer 1. Magnitude and direction of circulating currents measured for each
Section 11
1MRK 504 165-UUS -
Testing functionality by secondary injection
256
Transformer protection RET670 2.2 ANSI
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...