Table 27:
Test points for phase-to-phase loops A-B
Test point
Value
Comments
1
X
X1
R
0
2
X
0
R
RLdFwd
3
X
0.85·X1
R=0.491·X1+0.5 RFLdFwdPP
R
0.85·X1·1/tan(60°)+0.5
RFLdFwdPP
4
X
0.85·X1
R
-0.85·X1·tan (AngNegRes-90°)
5
X
0.5·RFLdFwdPP·tan (ArgLd)
R
0.5·RFLdFwdPP
6
X
-0.5·RLdFwd·tan (ArgDir)
R
0.5·RLdFwd
The table showing test points for phase-to-phase loops is used together with figure
.
11.4.6.1
Measuring the operating limit of set values
Procedure:
1.
Supply the IED with healthy conditions for at least two seconds.
2.
Apply the fault condition and slowly decrease the measured impedance to find the
operate value for of the phase-to-ground loop ECG, test point 1, according to figure
. Compare the result of the measurement with the expected value according to
table
.
The corresponding binary signals that inform about the operation of the phase
selection measuring elements are available in the local HMI under
Main menu/Test/Function status/Impedance Protection/PhaseSelection(PDIS,
21)/FRPSPDIS:x
.
3.
Repeat steps
to find the operate values for the remaining test points according
to figure
and table
.
When the load encroachment characteristic is deliberately set very
high in order not to have an influence, then the test points 2 and 5 can
be replaced by test point 7.
4.
to find the operate value for the phase-to-phase fault in A - C
.
1MRK 504 165-UUS -
Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI
131
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...