11.4.2
Phase selection, quad, fixed angle, load encroachment
FDPSPDIS (21)
Prepare the IED for verification of settings outlined in Section
The phase selectors operate on the same measuring principles as the impedance measuring
zones. So it is necessary to follow the same principles as for distance protection, when
performing the secondary injection tests.
Measure operating characteristics during constant current conditions. Keep the measured
current as close as possible to the rated value of its associated input transformer, or lower.
But ensure that it is higher than the set minimum operating current.
Ensure that the maximum continuous current to the IED does not exceed four times its
rated value, if the measurement of the operating characteristics runs under constant
voltage conditions.
To verify the settings the operating points according to figures
should be tested.
for information.
R
X
RFltFwdPG
1
3
)
1
(
XN
X
+
5
2
4
ArgNegRes
85%
50% of
RLdFwd
6
ANSI09000734-2-en.vsd
)
/
(
loop
W
)
/
(
loop
W
7
ANSI09000734 V2 EN
Figure 25:
Operating characteristic for phase selection function, forward direction
single-phase faults
Section 11
1MRK 504 165-UUS -
Testing functionality by secondary injection
118
Transformer protection RET670 2.2 ANSI
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...