I
tfs
= 0 A
•
State 2: main test step.
Define the following three-phase symmetrical quantities (the phase angle is related to
phase L1):
V
V
V
V
V
ts
t RvsZ
VT s
VT p
=
×
×
=
×
×
=
1 1
1 1 5899
0 1
13 8
47 02
.
.
.
.
.
,
,
,
EQUATION14069 V1 EN
(Equation 73)
29.60
arctan
180
arctan
180
90.56
0.29
ts
ReverseX
V
ReverseR
Ð
=
-
° =
-
° = -
°
æ
ö
æ
ö
ç
÷
ç
÷
è
ø
è
ø
EQUATION14068 V1 EN
(Equation 74)
frequency of V
ts
= 50 Hz
I
I
I
I
A
s
CTs
CTp
50
50
10459
1
9000
1 162
=
×
=
×
=
.
EQUATION14059 V1 EN
(Equation 75)
∠
I
50s
= 0º
frequency of I
50s
= 50 Hz
It
I
I
I
A
fs
CTs
CTp
tf
=
×
=
×
=
10459
1
9000
1 162
.
EQUATION14062 V1 EN
(Equation 76)
∠
I
tfs
= 180º
frequency of I
tfs
= 50.5 Hz
Expected result: the protection function does not issue either start or trip.
After each test it is possible to download and study the related disturbance recording.
1MRK 504 165-UUS -
Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI
169
Commissioning manual