Figure 41:
Boolean output signals for the injected current with two components: a 50
Hz current component and a 49.5 Hz current component
11.4.13
Automatic switch onto fault logic ZCVPSOF
Prepare the IED for verification of settings outlined in Section
The automatic switch onto fault logic function ZCVPSOF is checked using secondary
injection tests. ZCVPSOF is activated either by the external input
BC
or by the internal
DLD. FUFSPVC is done with a pre-fault condition where the phase voltages and currents
are at zero. A three-phase fault with zero impedance and a three-phase fault with an
impedance corresponding to the whole line is applied. This fault shall cause an
instantaneous trip and result in a
TRIP
indication.
11.4.13.1
Activating ZCVPSOF externally
Section 11
1MRK 504 165-UUS -
Testing functionality by secondary injection
170
Transformer protection RET670 2.2 ANSI
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...