values and respective compensating factors, and is therefore more complex for greater
than two transformers.
1.
Confirm that
OperationPAR
is set to
CC
for the transformers in the parallel group.
2.
For parallel operation, it is also recommended that settings be confirmed for parallel
group membership, governed by setting
TnRXOP
in the local HMI under
Main
menu/Settings/Setting group N/Control/TransformerVoltageControl(ATCC,
90)/TR8ATCC:x/ParCtrl
The general parallel arrangement of transformers are defined by setting
TnRXOP
to
Enabled
or
Disabled
. The following rules are applicable on the settings
T1RXOP
-
T4RXOP
.
If IED
T1
and
T2
are connected,
•
T1RXOP
shall be set to
Enabled
in instance 2 of TR8ATCC (90), and
•
T2RXOP
shall be set to
Enabled
in instance 1 of TR8ATCC (90).
If
T1
-
T3
are available,
•
T1RXOP
and
T2RXOP
shall be set to
Enabled
in instance 3 of TR8ATCC
(90),
•
T2RXOP
and
T3RXOP
shall be set to
Enabled
in instance 1 of TR8ATCC (90)
and so on.
The parameter corresponding to the own IED
must not
be set.
T1RXOP
should thus
not
be set in IED
T1
,
T2RXOPnot
in IED
T2
and so on.
3.
Review the settings for
VDeadband
(based on percentage of nominal bus voltage)
and calculate the upper (V2) and lower (V1) voltage regulation limits for which a tap
change command will be issued from the master transformer in the group.
4.
Review the expected time for first (
t1
) and subsequent (
t2
) tap change commands
from the master transformer in the local HMI under
Main menu/Settings/Setting
group N/TransformerVoltageControl(ATCC,90)/TR1ATCC:x/TR8ATCC:x/
Time/t1 and t2
5.
Inject a voltage V
B
equal to
VSet
for each transformer.
6.
Inject a load current for Transformer 1 that is equal to rated load current
I2Base
and
a load current for Transformer 2 that is equal to 95% of rated load current
I2Base
.
This will have the effect of producing a calculated circulating current that flows from
HV to LV side for Transformer 1 and LV to HV side for Transformer 2.
7.
Confirm that a circulating current is measured on the local HMI that is equal in
magnitude to 5% of
I2Base
, with polarity as discussed in step
.
8.
Confirm the settings for C
i
(Compensation Factor) and X
i
(Transformer Short
Circuit Impedance). Using these setting values and the measured quantity of
circulating current from the local HMI (I
cc_i
), calculate the value for circulating
current voltage adjustment V
ci
.
1MRK 504 165-UUS -
Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI
255
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...