If the function LDC is set to
Zero
, this test is omitted.
2.
Open the voltage control display on the LHMI in
Main Menu/Control/
Commands/TransformerVoltageControl (ATCC, 90)
.
IEC13000251-1-en.vsd
3.
In this view, check the following settings:
3.1. Check that
Control Mode
is set to
Manual
.
3.2. Operate the tap changer so that the
Load Voltage
corresponds to the
Voltage
Set Point
.
3.3. Check that neither the Raise or the Lower command are operating.
Voltage
Deviation
should be less than 100%.
3.4. Compare the values of
Bus Voltage
and
Load Voltage
.
UL can be obtained by a vector calculation where IL is the load current and
values for RL and XL are the settings given in primary system ohms.
~
L
o
a
d
R
L
X
L
V
B
V
L
V
B
R
L
I
L
jX
L
I
L
Re
ANSI06000487-2-en.vsd
For inductive load, the
Bus Voltage
should be higher than the
Load Voltage
. If not, current
circuits are incorrect and must be reversed. Incorrect current polarity may be an issue with
Section 12
1MRK 504 165-UUS -
Primary injection testing
288
Transformer protection RET670 2.2 ANSI
Commissioning manual