2
2
3
A
B
C
V
V
a V
a V
×
=
+
×
+ ×
EQUATION1818-ANSI V1 EN
(Equation 104)
Where:
A
B
C
and
V V
V
EQUATION1820-ANSI V1 EN
are the measured phase voltages
2
3
3
1
0, 5
2
j
a
e
j
p
×
= ×
= -
+
.
IECEQUATION00022 V2 EN
4.
Compare the result with the set value of the negative-sequence operating voltage
(consider that the set value
3V2PU
is in percentage of the base voltage
VBase
).
5.
Repeat steps
. Then slowly increase the measured current in one phase until
the BLKV signal disappears.
6.
Record the measured current and calculate the corresponding negative-sequence
current according to the equation (observe that the currents in the equation are
phasors):
2
2
3
A
B
C
I
I
a I
a I
×
=
+
×
+ ×
ANSIEQUATION00021 V1 EN
(Equation 105)
Where:
A
B
C
I
I and I
,
ANSIEQUATION00020 V1 EN
are the measured phase currents
2
3
3
1
0, 5
2
j
a
e
j
p
×
= ×
= -
+
.
IECEQUATION00022 V2 EN
7.
Compare the result with the set value of the negative-sequence operating current.
Consider that the set value
3I2<
is in percentage of the base current
IBase
.
11.9.2.3
Measuring the trip value for the zero-sequence function
Measure the trip value for the zero-sequence function, if included in the IED.
Section 11
1MRK 504 165-UUS -
Testing functionality by secondary injection
232
Transformer protection RET670 2.2 ANSI
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...