11.9.2
Application
The function TEIGGIO is used for user defined logics and it can also be used for different
purposes internally in the IED . An application example is the integration of elapsed time
during the measurement of neutral point voltage or neutral current at earth fault
conditions.
Settable time limits for warning and alarm are provided. The time limit for overflow
indication is fixed.
11.9.3
Setting guidelines
The settings
tAlarm
and
tWarning
are user settable limits defined in seconds. The
achievable resolution of the settings depends on the level of the values defined.
A resolution of 10 ms can be achieved when the settings are defined within the range
1.00
second ≤
tAlarm
≤
99 999.99
seconds
1.00
second ≤
tWarning
≤
99 999.99
seconds.
If the values are above this range the resolution becomes lower
99 999.99
seconds ≤
tAlarm
≤
999 999.9
seconds
99 999.99
seconds≤
tWarning
≤
999 999.9
seconds
Note that
tAlarm
and
tWarning
are independent settings, that is, there is no
check if
tAlarm
>
tWarning
.
tOverflow
is for overflow supervision with a default value
tOverflow
=
999 999.9
seconds.
The outputs freeze if an overflow occurs.
1MRK 511 286-UUS A
Section 11
Logic
281
Application manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Page 2: ......
Page 26: ...20...
Page 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Page 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Page 82: ...76...
Page 92: ...86...
Page 170: ...164...
Page 176: ...170...
Page 274: ...268...
Page 288: ...282...
Page 350: ...344...
Page 369: ...363...