2ndHarmStab
: The rate of 2nd harmonic current content for activation of the 2nd
harmonic restrain signal, to block chosen steps. The setting is given in % of the
fundamental frequency residual current. The setting range is
5 - 100
% in steps of 1%. The
default setting is 20% and can be used if a deeper investigation shows that no other value
is needed..
HarmRestrainx
: This parameter can be set
Disabled
/
Enabled
, to disable or enable the 2nd
harmonic restrain.
The four step phase overcurrent protection 3-phase output can be used in different ways,
depending on the application where the protection is used. A general description is given
below.
The pickup current setting of the inverse time protection, or the lowest current step of the
definite time protection, must be defined so that the highest possible load current does not
cause protection operation. Here consideration also has to be taken to the protection reset
current, so that a short peak of overcurrent does not cause operation of the protection even
when the overcurrent has ceased. This phenomenon is described in figure
.
Pickup current
Current I
The IED does not reset
Line phase current
Time t
Reset current
ANSI09000146-en-1.vsd
ANSI09000146 V1 EN
Figure 37:
Pickup and reset current for an overcurrent protection
The lowest setting value can be written according to equation
.
1MRK 511 286-UUS A
Section 6
Current protection
97
Application manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Page 2: ......
Page 26: ...20...
Page 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Page 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Page 82: ...76...
Page 92: ...86...
Page 170: ...164...
Page 176: ...170...
Page 274: ...268...
Page 288: ...282...
Page 350: ...344...
Page 369: ...363...