Events are also generated:
•
whenever any setting in the IED is changed.
The internal events are time tagged with a resolution of 1 ms and stored in a list. The list
can store up to 40 events. The list is based on the FIFO principle, that is, when it is full, the
oldest event is overwritten. The list can be cleared via the local HMI .
The list of internal events provides valuable information, which can be used during
commissioning and fault tracing.
15.2
Time synchronization
15.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time synchronization
TIMESYNCHGE
N
-
-
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time system, summer time begins
DSTBEGIN
-
-
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time system, summer time ends
DSTEND
-
-
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time synchronization via IRIG-B
IRIG-B
-
-
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time synchronization via SNTP
SNTP
-
-
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time zone from UTC
TIMEZONE
-
-
Section 15
1MRK 511 286-UUS A
Basic IED functions
326
Application manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Page 2: ......
Page 26: ...20...
Page 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Page 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Page 82: ...76...
Page 92: ...86...
Page 170: ...164...
Page 176: ...170...
Page 274: ...268...
Page 288: ...282...
Page 350: ...344...
Page 369: ...363...