Open
Disconnector
IED
ANSI11000172_1_en.vsd
ANSI11000172 V1 EN
Figure 58:
Typical connection for stub protection in breaker-and-a-half
arrangement.
6.8.3
Setting guidelines
The parameters for Stub protection STBPTOC (50STB) are set via the local HMI or
PCM600.
The following settings can be done for the stub protection.
GlobalBaseSel
: Selects the global base value group used by the function to define (
IBase
),
(
VBase
) and (
SBase
).
Operation
:
Disabled
/
Enabled
1MRK 511 286-UUS A
Section 6
Current protection
135
Application manual