LOCK
Binary input signal that will activate/deactivate the function, defined in ACT or SMT.
ACTIVE
Output status signal
OVERRIDE
Set if function is overridden
When CHNGLCK has a logical one on its input, then all attempts to modify the IED
configuration and setting will be denied and the message "Error: Changes blocked" will
be displayed on the local HMI; in PCM600 the message will be "Operation denied by
active ChangeLock". The CHNGLCK function should be configured so that it is
controlled by a signal from a binary input card. This guarantees that by setting that signal
to a logical zero, CHNGLCK is deactivated. If any logic is included in the signal path to
the CHNGLCK input, that logic must be designed so that it cannot permanently issue a
logical one to the CHNGLCK input. If such a situation would occur in spite of these
precautions, then please contact the local ABB representative for remedial action.
15.5.3
Setting guidelines
The Change lock function CHNGLCK does not have any parameters available in the local
HMI or PCM600.
15.6
IED identifiers TERMINALID
15.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IED identifiers
TERMINALID
-
-
15.6.2
Application
15.6.2.1
Customer specific settings
The customer specific settings are used to give the IED a unique name and address. The
settings are used by a central control system to communicate with the IED. The customer
specific identifiers are found in the local HMI under
Configuration/Power system/
Identifiers/TERMINALID
The settings can also be made from PCM600. For more information about the available
identifiers, see the technical manual.
Section 15
1MRK 511 286-UUS A
Basic IED functions
332
Application manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Page 2: ......
Page 26: ...20...
Page 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Page 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Page 82: ...76...
Page 92: ...86...
Page 170: ...164...
Page 176: ...170...
Page 274: ...268...
Page 288: ...282...
Page 350: ...344...
Page 369: ...363...