9.1.3
Setting guidelines
GlobalBaseSel
: Selects the global base value group used by the function to define (
IBase
),
(
VBase
) and (
SBase
).
Current circuit supervision CCSRDIF (87) compares the residual current from a three-
phase set of current transformer cores with the neutral point current on a separate input
taken from another set of cores on the same current transformer.
The minimum operate current,
IMinOp
, must be set as a minimum to twice the residual
current in the supervised CT circuits under normal service conditions and rated primary
current.
The parameter
Pickup_Block
is normally set at
150%
to block the function during
transient conditions.
The FAIL output is connected in the PCM configuration to the blocking input of the
protection function to be blocked at faulty CT secondary circuits.
9.2
Fuse failure supervision SDDRFUF
9.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fuse failure supervision
SDDRFUF
-
-
9.2.2
Application
Different protection functions within the protection IED, operates on the basis of the
measured voltage in the relay point. Examples are:
•
impedance protection functions
•
undervoltage function
•
energizing check function and voltage check for the weak infeed logic
These functions can operate unintentionally if a fault occurs in the secondary circuits
between the voltage instrument transformers and the IED.
It is possible to use different measures to prevent such unwanted operations. Miniature
circuit breakers in the voltage measuring circuits, located as close as possible to the
voltage instrument transformers, are one of them. Separate fuse-failure monitoring IEDs
or elements within the protection and monitoring devices are another possibilities. These
Section 9
1MRK 511 286-UUS A
Secondary system supervision
172
Application manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Page 2: ......
Page 26: ...20...
Page 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Page 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Page 82: ...76...
Page 92: ...86...
Page 170: ...164...
Page 176: ...170...
Page 274: ...268...
Page 288: ...282...
Page 350: ...344...
Page 369: ...363...