![background image](http://html1.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_applications-manual_3390438300.webp)
12.6
Limit counter L4UFCNT
12.6.1
Function description
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Limit counter
L4UFCNT
-
12.6.2
Application
Limit counter (L4UFCNT) is intended for applications where positive and/or negative
flanks on a binary signal need to be counted.
The limit counter provides four independent limits to be checked against the accumulated
counted value. The four limit reach indication outputs can be utilized to initiate
proceeding actions. The output indicators remain high until the reset of the function.
It is also possible to initiate the counter from a non-zero value by resetting the function to
the wanted initial value provided as a setting.
If applicable, the counter can be set to stop or rollover to zero and continue counting after
reaching the maximum count value. The steady overflow output flag indicates the next
count after reaching the maximum count value. It is also possible to set the counter to
rollover and indicate the overflow as a pulse, which lasts up to the first count after rolling
over to zero. In this case, periodic pulses will be generated at multiple overflow of the
function.
12.6.2.1
Setting guidelines
The parameters for Limit counter L4UFCNT are set in the local HMI or PCM600.
Section 12
1MRK 511 286-UUS A
Monitoring
294
Application manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Page 2: ......
Page 26: ...20...
Page 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Page 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Page 82: ...76...
Page 92: ...86...
Page 170: ...164...
Page 176: ...170...
Page 274: ...268...
Page 288: ...282...
Page 350: ...344...
Page 369: ...363...