A positive value of current, power, and so on (forward) means that the quantity has a
direction towards the object. - A negative value of current, power, and so on (reverse)
means a direction away from the object. See figure
Protected Object
Line, transformer, etc
Forward
Reverse
Definition of direction
for directional functions
Measured quantity is
positive when flowing
towards the object
e.g. P, Q, I
Reverse
Forward
Definition of direction
for directional functions
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object
Set parameter
CTStarPoint
Correct Setting is
"ToObject"
Set parameter
CTStarPoint
Correct Setting is
"FromObject"
en05000456-2.vsd
ANSI05000456 V2 EN
Figure 15:
Internal convention of the directionality in the IED
With correct setting of the primary CT direction,
CT_WyePoint
set to
FromObject
or
ToObject
, a positive quantity always flows towards the protected object and a direction
defined as Forward is always looking towards the protected object. The following
examples show the principle.
4.2.3.1
Example 1
Two IEDs used for protection of two objects.
1MRK 511 286-UUS A
Section 4
Analog inputs
63
Application manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Page 2: ......
Page 26: ...20...
Page 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Page 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Page 82: ...76...
Page 92: ...86...
Page 170: ...164...
Page 176: ...170...
Page 274: ...268...
Page 288: ...282...
Page 350: ...344...
Page 369: ...363...