Figure 7:
Inverse time operation characteristics for selectivity
3.1.5
Calculating settings for four step phase overcurrent protection
3-phase output, LV-side OC4PTOC (51_67)
The 22 kV phase overcurrent protection has the following purpose:
•
Main protection for short circuits on 22 kV busbar
•
Backup protection for short circuits on outgoing 22 kV feeders (if possible)
The reach of the phase overcurrent line protection is dependent on the operation state and
the fault type. Therefore the setting must be based on fault calculations made for different