Set value
Mode
Formula used for complex power calculation
A
*
A
A
S 3 V
I
= ×
×
EQUATION2044 V1 EN
(Equation 65)
B
*
B
B
S 3 V
I
= ×
×
EQUATION2045 V1 EN
(Equation 66)
C
*
C
C
S 3 V
I
= ×
×
EQUATION2046 V1 EN
(Equation 67)
The function has two stages that can be set independently.
With the parameter
OpMode1(2)
the function can be set
Enabled
/
Disabled
.
The function gives trip if the power component in the direction defined by the setting
Angle1(2)
is larger than the set pick up power value
Power1(2)
Section 6
1MRK 511 286-UUS A
Current protection
142
Application manual