GblBaseSelLine
) which independently of each other can be set to select one of the six
GBASVAL functions used for reference of base values. This means that the reference
voltage of bus and line can be set to different values. The settings for the SESRSYN (25)
function found under
Main menu/Settings/Control/SESRCYN(25,SYNC)/
X:SESRSYN
has been divided into four different setting groups: General,
Synchronizing, Synchrocheck and Energizing check.
General settings
Operation
: The operation mode can be set
Enabled
or
Disabled
. The setting
Disabled
disables the whole function.
GblBaseSelBus
and
GblBaseSelLine
These configuration settings are used for selecting one of six GBASVAL functions; the
base voltage
UBase
of the set Global Base Value group is used as base value of the voltage,
for bus and line respectively.
SelPhaseBus1
and
SelPhaseBus2
Configuration parameters for selection of measuring phase of the voltage for the busbar 1
and 2 respectively, which can be a single-phase (phase-neutral) or two-phase (phase-
phase) voltage or positive sequence.
SelPhaseLine1
and
SelPhaseLine2
Configuration parameters for selection of measuring phase of the voltage for line 1 and 2
respectively, which can be a single-phase (phase-neutral) or two-phase (phase-phase)
voltage or positive sequence.
CBConfig
This configuration setting is used to define type of voltage selection. Type of voltage
selection can be selected as:
•
no voltage selection
•
single circuit breaker with double bus
•
breaker-and-a-half arrangement with the breaker connected to busbar 1
•
breaker-and-a-half arrangement with the breaker connected to busbar 2
•
breaker-and-a-half arrangement with the breaker connected to line 1 and 2 (tie
breaker)
VRatio
The
VRatio
is defined as
VRatio
=
bus voltage
/
line voltage
. This setting scales up the line
voltage to an equal level with the bus voltage.
PhaseShift
1MRK 511 286-UUS A
Section 10
Control
193
Application manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Page 2: ......
Page 26: ...20...
Page 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Page 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Page 82: ...76...
Page 92: ...86...
Page 170: ...164...
Page 176: ...170...
Page 274: ...268...
Page 288: ...282...
Page 350: ...344...
Page 369: ...363...