Data conversion if parameter
is set to
. See section
About the control profiles (page 612)
2
If parameter
is set to
,
3
•
The sources of the status word and actual values are selected by parameters
(otherwise, actual values 1 and 2 are automatically selected ac-
cording to reference type), and
•
The control word is displayed by
6.5 EFB transparent control word
■
Control word and Status word
The Control Word (CW) is a 16-bit or 32-bit packed boolean word. It is the principal
means of controlling the drive from a fieldbus system. The CW is sent by the
fieldbus controller to the drive. By drive parameters, the user selects the EFB CW
as the source of drive control commands (such as start/stop, emergency stop,
selection between external control locations 1/2, or fault reset). The drive switches
between its states according to the bit-coded instructions of the CW.
The fieldbus CW is either written to the drive as it is (see parameter
), or the data is converted. See section
The fieldbus Status Word (SW) is a 16-bit or 32-bit packed boolean word. It contains
status information from the drive to the fieldbus controller. The drive SW is either
written to the fieldbus SW as it is or the data is converted. See section
■
References
EFB references 1 and 2 are 16-bit or 32-bit signed integers. The contents of each
reference word can be used as the source of virtually any signal, such as the speed,
frequency, torque or process reference. In embedded fieldbus communication,
references 1 and 2 are displayed by
and
respectively. Whether the references are scaled or not depends on the settings of
and
. See section
■
Actual values
Fieldbus actual signals (ACT1 and ACT2) are 16-bit or 32-bit signed integers. They
convey selected drive parameter values from the drive to the master. Whether the
actual values are scaled or not depends on the settings of
and
. See section
About the control profiles (page 612)
■
Data input/outputs
Data input/outputs are 16-bit or 32-bit words containing selected drive parameter
values. Parameters
…
define the addresses
from which the master either reads data (input) or to which it writes data (output).
Fieldbus control through the embedded fieldbus interface (EFB) 611
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...