Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
- / -
Data to be sent as word 1 in master/follower
communication.
0...65535
- / uint16
Displays the data to be sent onto the master/follower
link as word 2 as an integer.
If no data has been preselected by
, the value to be sent can be written directly
into this parameter.
M/F data 2 value
61.26
- / -
Data to be sent as word 2 in master/follower
communication.
0...65535
- / uint16
Displays the data to be sent onto the master/follower
link as word 3 as an integer.
If no data has been preselected by
, the value to be sent can be written directly
into this parameter.
M/F data 3 value
61.27
- / -
Data to be sent as word 3 in master/follower
communication.
0...65535
None / uint32
Parameters
preselect data to be sent in
data sets 2 and 4 to the external controller. These data
sets are used in ModuleBus communication with a
“standard drive” (
60.50 DDCS controller drive type
=
). Parameters
…
display
the data to be sent to the external controller. If no data
has been preselected, the value to be sent can be
written directly into these parameters. For example,
this parameter preselects the data for word 1 of data
set 2. Parameter
displays
the selected data in integer format. If no data is
preselected, the value to be sent can be written directly
into parameter
.
Data set 2 data 1
selection
61.45
0
None.
None
1
Control Word (16 bits)
CW 16bit
4
Status Word (16 bits)
SW 16bit
5
Actual value ACT1 (16 bits)
Act1 16bit
6
Actual value ACT2 (16 bits)
Act2 16bit
See
Terms and abbreviations (page 130)
.
Other [value]
None / uint32
Preselects the data to be sent as word 2 of data set 2
to the external controller.
See also parameter
.
For the selections, see parameter
.
Data set 2 data 2
selection
61.46
None / uint32
See parameter
61.45 Data set 2 data 1 selection
Data set 2 data 3
selection
61.47
…
…
…
…
None / uint32
See parameter
61.45 Data set 2 data 1 selection
Data set 4 data 3
selection
61.50
Parameters 425
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...