Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
3
Motor overload class 30.
Class 30
4
Motor overload class 40.
Class 40
0.0 % / real32
Shows the calculated temperature of the motor cable.
See section
.
102% = overtemperature warning (
)
106% = overtemperature fault (
)
This parameter is read-only.
Cable temperature
35.60
1 = 1 % / 10 = 1 %
Calculated temperature of motor cable.
0.0 ... 200.0 %
10000.00 A / real32
Specifies the continuous current of the motor cable
for the thermal protection function in the control
program.
WARNING!
The value entered in this parameter must be
limited according to all factors affecting the
loadability of the cable, such as ambient
temperature, cabling arrangement, and
shrouding. Refer to the technical data from the
cable manufacturer.
Cable nominal
current
35.61
1 = 1 A / 100 = 1 A
Continuous current-carrying capacity of motor cable.
0.00 ... 10000.00 A
Parameters 351