forced I/O values such as parameters
and
•
I/O extension module settings (groups 14…16)
•
fieldbus communication enable parameters (
and
)
•
other fieldbus communication settings (groups 51…56 and 58)
•
encoder configuration settings (groups 92…93),
•
some hardware settings in parameter group
, and
•
user set selection parameters
…
As the motor settings are included in the user parameter sets, make sure the
settings correspond to the motor used in the application before recalling a user
set. In an application where different motors are used with the drive, the motor
ID run needs to be performed with each motor and the results saved to different
user sets. The appropriate set can then be recalled when the motor is switched.
If no parameter sets have been saved, attempting to load a set will create all sets
from the currently active parameter settings.
Switching between user parameter sets is only possible with the drive stopped.
Settings and diagnostics
Parameters:
10.3 DI force selection (page 173)
,
,
, and
…
96.13 User set I/O mode in2 (page 520)
.
Parameter group:
95 HW configuration (page 507)
.
Events:
64B2 User set fault (page 562)
■
Parameter checksum calculation
A parameter checksum can be calculated from a user-definable set of parameters
to monitor changes in the drive configuration. The calculated checksum is
compared to 1…4 reference checksums; in case of a mismatch, an event (a pure
event, warning or fault) is generated.
By default, the set of parameters included in the calculation contain most
parameters with the exception of
•
actual signals
•
parameter group
•
parameters that are activated to validate new settings (such as
and
•
parameters that are not saved to the flash memory (such as
•
parameters that are internally calculated from others (such as
).
•
dynamic parameters (eg. parameters that vary according to hardware), and
Program features 121
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...