
Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Disable; Enable
(95.20 b5) / uint16
(Only visible with a ZCU control unit)
Enables/disables DC switch monitoring via the DIIL
input. This setting is intended for use with inverter
modules with an internal charging circuit that are
connected to the DC bus through a DC switch.
An auxiliary contact of the DC switch must be wired to
the DIIL input so that the input switches off when the
DC switch is opened.
M
+2
4
V
DIIL
DC bus
DC switch
Inverter module
Charging
contactor
Charging logic
If the DC switch is opened with the inverter running,
the inverter is given a coast-to-stop command, and its
charging circuit activated.
Starting the inverter is prevented until the DC switch
is closed and the DC circuit in the inverter unit
recharged.
Note: By default, DIIL is the input for the Run enable
signal. Adjust
if necessary.
Note: An internal charging circuit is standard on some
inverter module types but optional on others; check
with your local ABB representative.
DC switch
monitoring
95.8
0
DC switch monitoring through the DIIL input disabled.
Disable
1
DC switch monitoring through the DIIL input enabled.
Enable
Parameters 509
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...