deviation from the expected deceleration rate. If the drive fails to stop in the
expected manner, a fault is generated and the drive coasts to a stop.
Main cooling fan supervision (parameter
31.35)
The parameter selects how the drive reacts to a loss of the main cooling fan.
With an inverter unit consisting of frame R8i inverter modules, it may be possible
to continue operation even if a cooling fan of an inverter module stops. See the
description of the parameter.
Custom motor current fault limit (parameter
31.42)
The control program sets a motor current limit based on drive hardware. In most
cases, the default value is appropriate. However, a lower limit can be manually set
by the user, for example, to protect a permanent magnet motor from
demagnetization.
Local control loss detection (parameter
49.05)
The parameter selects how the drive reacts to a control panel or PC tool
communication break.
Diagnostics
■
Fault and warning messages, data logging
See chapter
■
Signal supervision
Three signals can be selected to be supervised by this function. Whenever a
supervised signal exceeds or falls below predefined limits, a bit in
is activated,
and a warning or fault generated. The contents of the message can be edited on
the control panel by selecting Menu - Settings - Edit texts.
The supervised signal is low-pass filtered. The supervision operates on a 2 ms time
level. The configuration parameters are scanned for changes on a 10 ms time level.
Settings and diagnostics
Parameter group:
.
Events:
A8B0 Signal supervision (page 587)
A8B1 Signal supervision 2 (page 587)
A8B2 Signal supervision 3 (page 587)
,
80B0 Signal supervision (page 569)
and
80B2 Signal supervision 3 (page 569)
.
■
Maintenance timers and counters
The program has six different maintenance timers or counters that can be
configured to generate a warning when a pre-defined limit is reached. The contents
118 Program features
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...