Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
-600.00 % / real32
Defines the maximum shaft power for generating upon
a supply network failure when supply unit control is
active (bit 15 of
is on).
The value is given in percent of nominal motor power.
Note: With a diode supply unit (bit 11 of
is on),
the motoring shaft power is limited to 2% upon a
network failure regardless of this parameter.
Power gen limit on
net loss
94.41
1 = 1 % / 100 = 1 %
Maximum shaft power for generating mode upon a
supply network failure.
-600.00 ... 0.00 %
506 Parameters