Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
- / real32
Maximum torque reference for speed controller
adaptation.
Speed controller gain can be adapted according to the
final unlimited torque reference (
).
This can be used to smooth out disturbances caused
by a small load and backlashes.
The functionality involves multiplying the gain (
) by a coefficient within a
certain torque range.
When the torque reference is 0%, the gain is multiplied
by the value of parameter
When the torque reference is equal to or above
, no adaptation takes place (the
coefficient is 1).
Between 0% and
, the
coefficient for the gain is calculated linearly on the basis
of the breakpoints.
Filtering can be applied on the torque reference using
parameter
See also the block diagram on page
.
1.000
25.27
Coefficient for K
p
(proportional gain)
Final torque reference
(
26.01) (rpm)
25.25
0
Torque adapt max
limit
25.25
- / -
Maximum torque reference for speed controller
adaptation. For scaling, see parameter
.
0.0 ... 1600.0 %
0.000 s / real32
Defines a filter time constant for the adaptation, in
effect adjusting the rate of change of the gain.
See parameter
Torque adapt filt
time
25.26
100 = 1 s / 1000 = 1 s
Filter time for adaptation.
0.000 ... 100.000 s
1.000 / real32
Proportional gain coefficient at 0% torque reference.
See parameter
Kp adapt coef at min
torque
25.27
1000 = 1 / 1000 = 1
Proportional gain coefficient at 0% torque reference.
0.000 ... 10.000
292 Parameters
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...