Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
- / uint16
(Only visible when IGBT supply unit control activated
by
)
Displays limit word 4 of the supply unit.
This parameter is read-only.
LSU limit word 4
30.104
1 = DC reference is being limited by supply control
program parameters
Udc ref max
b0
1 = DC reference is being limited by supply control
program parameters
Udc ref min
b1
1 = Current is being limited by supply control program
parameters
User I max
b2
1 = Current is being limited based on temperature
Temp I max
b3
Reserved
b4…15
1 = 1
0000h…FFFFh
-130.0 % / real32
(Only visible when IGBT supply unit control activated
by
)
Defines a minimum power limit for the supply unit.
Negative values refer to regenerating, ie. feeding power
into the supply network.
LSU minimum power
limit
30.148
1 = 1 % / 10 = 1 %
Minimum power limit for supply unit.
-200.0 ... 0.0 %
130.0 % / real32
(Only visible when IGBT supply unit control activated
by
)
Defines a maximum power limit for the supply unit.
LSU maximum
power limit
30.149
1 = 1 % / 10 = 1 %
Maximum power limit for supply unit.
0.0 ... 200.0 %
Parameters 315