1 s / uint16
Specifies the thermal time of the motor cable for the
thermal protection function in the control program.
This value is defined as the time to reach 63% of the
nominal cable temperature when the cable is loaded
with nominal current (parameter
).
0 s = Thermal protection of motor cable disabled.
Refer to the technical data from the cable
manufacturer.
Cable current
Temperature rise
100%
100%
63%
Time
Time
Cable thermal time
Cable thermal rise
time
35.62
1 = 1 s / 1 = 1 s
0 s → Thermal protection of motor cable disabled.
1…50000 s → Motor cable thermal time constant.
0...50000 s
Off, 06.16 b6 (95.20
b6) / uint32
Parameters
configure a monitored
start/stop control logic for external equipment such
as a contactor controlled motor cooling fan.
This parameter selects the signal that starts and stops
the fan.
0 = Stop
1 = Start
The output controlling the fan contactor is to be
connected to parameter
, bit 1. On and off delays
can be set for the fan by
and
respectively.
A feedback signal from the fan can be connected to an
input selected by
; the loss of the feedback will
optionally trigger a warning or fault (see
and
).
DOL starter control
source
35.100
0
0 (function disabled).
Off
1
1.
On
2
Bit 6 of
6.16 Drive status word 1 (page 153)
.
Running
See
Terms and abbreviations (page 130)
Other [bit]
352 Parameters
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...