Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
5
Action is taken whenever the signal falls below its low
limit or rises above its high limit.
Both
6
Action is taken whenever the absolute value of the
signal falls below its (absolute) low limit or rises above
its (absolute) high limit.
Abs both
No action / uint16
Selects the action the drive takes when the value
monitored by signal supervision 2 exceeds its limits.
Note: This parameter does not affect the status
indicated by
Supervision 2 action
32.16
0
No action taken.
No action
1
A warning (
) is generated.
Warning
2
The drive trips on
Fault
3
If running, the drive trips on
Fault if running
Zero / uint32
Selects the signal to be monitored by signal supervision
function 2.
For the available selections, see parameter
Supervision 2 signal
32.17
0.000 s / real32
Defines a filter time constant for the signal monitored
by signal supervision 2.
Supervision 2 filter
time
32.18
1000 = 1 s / 1000 = 1
s
Signal filter time.
0.000 ... 30.000 s
0.00 / real32
Defines the lower limit for signal supervision 2.
Supervision 2 low
32.19
- / -
Low limit.
-21474830.00 ...
21474830.00
0.00 / real32
Defines the upper limit for signal supervision 2.
Supervision 2 high
32.20
- / -
Upper limit.
-21474830.00 ...
21474830.00
Disabled / uint16
Selects the mode of signal supervision function 3.
Determines how the monitored signal (see parameter
) is compared to its lower and upper limits (
and
respectively).
The action to be taken when the condition is fulfilled
is selected by
Supervision 3
function
32.25
0
Signal supervision 3 not in use.
Disabled
1
Action is taken whenever the signal falls below its lower
limit.
Low
2
Action is taken whenever the signal rises above its
upper limit.
High
3
Action is taken whenever the absolute value of the
signal falls below its (absolute) lower limit.
Abs low
4
Action is taken whenever the absolute value of the
signal rises above its (absolute) upper limit.
Abs high
5
Action is taken whenever the signal falls below its low
limit or rises above its high limit.
Both
330 Parameters
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...