What to do
Cause
Event name /
Aux. code
Code
(hex)
try installing the module into a
different slot.
If the module is installed on an FEA-03
extension adapter, check the fiber
optic connections.
Check the auxiliary code (format XXXX
YYYY). “YYYY” indicates the problem
(see actions for each code below).
Contact your local ABB
representative.
Failed answer to encoder
configuration message.
0001
Contact your local ABB
representative.
Failed answer to adapter watchdog
disable message.
0002
Contact your local ABB
representative.
Failed answer to adapter watchdog
enable message.
0003
Contact your local ABB
representative.
Failed answer to adapter
configuration message.
0004
Contact your local ABB
representative.
Too many failed answers inline to
speed and position messages.
0005
Contact your local ABB
representative.
DDCS driver failed.
0006
Check the auxiliary code (format XXYY
YYYY). “XX” specifies the number of
The I/O extension module types
specified by parameters do not match
the detected configuration.
Ext I/O comm
loss
A799
the I/O extension module (01:
parameter group
, 02:
2, 03:
“YY YYYY” indicates the problem (see
actions for each code below).
Check that the module is properly
seated in its slot.
Communication with module failed.
00 0001
Check that the module and the slot
connector is not damaged.
Try installing the module into
another slot.
Check the type and location settings
of the modules (parameters
or
Module not found.
00 0002
Check that the module is properly
seated in its slot.
Check that the module and the slot
connector is not damaged.
Try installing the module into
another slot.
Check the type and location settings
of the modules (parameters
or
Configuration of module failed.
00 0003
Check that the module is properly
seated in its slot.
Check that the module and the slot
connector is not damaged.
Try installing the module into
another slot.
580 Fault tracing
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...