
Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
256 s / uint16
Defines the thermal time constant for use with the
motor thermal protection model, defined as the time
to reach 63% of the nominal motor temperature. See
the motor manufacturer's recommendations.
Motor current
Temperature rise
Time
Time
100%
100%
63%
Motor thermal time
Motor thermal time
constant
35.55
1 = 1 s / 1 = 1 s
Motor thermal time constant.
100...10000 s
No action / uint16
Selects the action taken when motor overload is
detected.
See section
Motor overload protection (page 115)
.
Motor overload
action
35.56
0
No action taken.
No action
1
Drive generates warning
when
the motor is overloaded to the warning level, that is,
parameter
reaches value
88.0%.
Warning only
2
Drive generates warning
when
the motor is overloaded to the warning level, that is,
parameter
reaches value
88.0%.
Drive trips on fault
when the motor
is overloaded to the fault level, that is, parameter
reaches value 100.0%.
Warning and fault
Class 20 / uint16
Defines the motor overload class to be used. The class
of protection is specified by the user as the time for
tripping at 7.2 times (IEC 60947-4-1) or 6 times (NEMA
ICS) the tripping level current.
See section
Motor overload protection (page 115)
.
Motor overload class
35.57
0
Motor overload class 5.
Class 5
1
Motor overload class 10.
Class 10
2
Motor overload class 20.
Class 20
350 Parameters
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...