Resistor braking 165
Technical data
Ratings
P
brcont
Maximum continuous braking power. The braking is considered continuous if the braking time
exceeds 30 seconds.
R
min
The minimum allowed resistance value of the brake resistor
R
Resistance value for the listed resistor assembly
E
R
Short energy pulse that the resistor assembly withstands every 400 seconds
P
Rcont
Continuous power (heat) dissipation of the resistor when placed correctly
The ratings apply at an ambient temperature of 40 °C (104 °F). For 690 V data, please contact your local ABB
representative.
SAFUR resistors
The degree of protection of SAFUR resistors is IP00. The resistors are not UL listed. The
thermal time constant of the resistors is 555 seconds.
Drive module
unit type
ACS880-
07XT-
Basic module
type
ACS8880-04-
Internal brake
chopper per
basic brake
module
Example brake resistor(s) per basic module
P
brcont
R
min
Type
R
E
R
P
Rcont
kW
ohm
ohm
kJ
kW
U
N
= 400 V
1010A-3
585A-3+P943
315
1.3
2xSAFUR200F500
1.35
10800
27
1190A-3
650A-3+P943
315
1.3
2xSAFUR200F500
1.35
10800
27
1330A-3
725A-3+P943
400
0.7
3xSAFUR200F500
0.90
16200
40
1610A-3
880A-3+P943
400
0.7
3xSAFUR200F500
0.90
16200
40
U
N
= 500 V
1010A-5
583A-5+P943
315
1.3
2xSAFUR200F500
1.35
10800
27
1160A-5
635A-5+P943
315
1.3
2xSAFUR200F500
1.35
10800
27
1310A-5
715A-5+P943
400
0.7
3xSAFUR200F500
0.90
16200
40
1610A-5
880A-5+P943
400
0.7
3xSAFUR200F500
0.90
16200
40
U
N
= 690 V
0810A-7
430A-7+P943
285
2.2
SAFUR200F500
2.70
3600
13
0960A-7
522A-7+P943
350
2.0
2xSAFUR125F500
2.0
7200
18
1080A-7
590A-7+P943
400
1.8
2xSAFUR125F500
2.0
7200
18
1320A-7
721A-7+P943
400
1.8
2xSAFUR125F500
2.0
7200
18
3AXD10000363510, 3AXD00000588487
Summary of Contents for ACS880-07XT Series
Page 1: ...ABB industrial drives Hardware manual ACS880 07XT drives 400 to 1200 kW ...
Page 4: ......
Page 12: ...12 ...
Page 20: ...20 Safety instructions ...
Page 26: ...26 Introduction to the manual ...
Page 54: ...54 Mechanical installation ...
Page 89: ...Electrical installation 89 PE 11 8 4 9 11 ...
Page 94: ...94 Electrical installation ...
Page 112: ...112 Fault tracing ...
Page 123: ...Maintenance 123 5 6 7 ...
Page 124: ...124 Maintenance 8 10 9 ...
Page 126: ...126 Maintenance 6 5 4 ...
Page 127: ...Maintenance 127 9 8 7 ...
Page 128: ...128 Maintenance 12 11 10 ...
Page 149: ...Dimensions 149 Dimension drawing examples Frame 2 R11 R10 with brake chopper ...
Page 150: ...150 Dimensions Frame 2 R11 R10 without brake chopper ...
Page 153: ...Dimensions 153 Location of input terminals ACS880 07XT 12 pulse ...
Page 154: ...154 Dimensions Location of output terminals ACS880 07XT R10 with du dt ...
Page 155: ...Dimensions 155 Location of output terminals ACS880 07XT R10 without du dt ...
Page 156: ...156 Dimensions Location of output terminals ACS880 07XT R11 with du dt ...
Page 157: ...Dimensions 157 Location of output terminals ACS880 07XT R11 without du dt ...
Page 158: ...158 Dimensions Location of PE terminals ACS880 07XT ...
Page 159: ...Dimensions 159 Location of resistor terminals ACS880 07XT R10 ...
Page 160: ...160 Dimensions Location of resistor terminals ACS880 07XT R11 ...
Page 168: ...www abb com drives www abb com drivespartners 3ABD00043579 Rev C EN 2018 01 01 Contact us ...