60 Guidelines for planning the electrical installation
Additional requirements for explosion-safe (EX) motors
If you use an explosion-safe (EX) motor, obey the rules in the requirements table above. In
addition, consult the motor manufacturer for any further requirements.
Additional requirements for ABB motors of types other than M2_, M3_, M4_, HX_
and AM_
Use the selection criteria given for non-ABB motors.
Additional requirements for the braking applications
When the motor brakes the machinery, the intermediate circuit DC voltage of the drive
increases, the effect being similar to increasing the motor supply voltage by up to
20 percent. Consider this voltage increase when you specify the motor insulation
requirements if the motor is braking a large part of its operation time.
Example: Motor insulation requirement for a 400 V AC line voltage application must be
selected as if the drive were supplied with 480 V.
Additional requirements for ABB high-output and IP23 motors
The rated output power of high output motors is higher than what is stated for the particular
frame size in EN 50347:2001. This table shows the requirements for ABB random-wound
motor series (for example, M3AA, M3AP and M3BP).
Nominal AC supply
voltage
Requirement for
Motor insulation
system
ABB du/dt and common mode filters, insulated N-end
motor bearings
100 kW <
P
N
< 200 kW
P
N
> 200 kW
140 hp <
P
N
< 268 hp
P
N
> 268 hp
U
N
< 500 V
Standard
+ N
+ N + CMF
1)
500 V <
U
N
< 600 V Standard
+ d
u
/d
t
+ N
+ d
u
/d
t
+ N + CMF
or
Reinforced
+ N
+ N + CMF
1)
600 V <
U
N
< 690 V Reinforced
+ d
u
/d
t
+ N
+ d
u
/d
t
+ N + CMF
1)
also d
u
/d
t
filter is required at the output of the basic drive modules if the motor cable length is less
than 20 meters before connecting the motor cables together
Summary of Contents for ACS880-07XT Series
Page 1: ...ABB industrial drives Hardware manual ACS880 07XT drives 400 to 1200 kW ...
Page 4: ......
Page 12: ...12 ...
Page 20: ...20 Safety instructions ...
Page 26: ...26 Introduction to the manual ...
Page 54: ...54 Mechanical installation ...
Page 89: ...Electrical installation 89 PE 11 8 4 9 11 ...
Page 94: ...94 Electrical installation ...
Page 112: ...112 Fault tracing ...
Page 123: ...Maintenance 123 5 6 7 ...
Page 124: ...124 Maintenance 8 10 9 ...
Page 126: ...126 Maintenance 6 5 4 ...
Page 127: ...Maintenance 127 9 8 7 ...
Page 128: ...128 Maintenance 12 11 10 ...
Page 149: ...Dimensions 149 Dimension drawing examples Frame 2 R11 R10 with brake chopper ...
Page 150: ...150 Dimensions Frame 2 R11 R10 without brake chopper ...
Page 153: ...Dimensions 153 Location of input terminals ACS880 07XT 12 pulse ...
Page 154: ...154 Dimensions Location of output terminals ACS880 07XT R10 with du dt ...
Page 155: ...Dimensions 155 Location of output terminals ACS880 07XT R10 without du dt ...
Page 156: ...156 Dimensions Location of output terminals ACS880 07XT R11 with du dt ...
Page 157: ...Dimensions 157 Location of output terminals ACS880 07XT R11 without du dt ...
Page 158: ...158 Dimensions Location of PE terminals ACS880 07XT ...
Page 159: ...Dimensions 159 Location of resistor terminals ACS880 07XT R10 ...
Page 160: ...160 Dimensions Location of resistor terminals ACS880 07XT R11 ...
Page 168: ...www abb com drives www abb com drivespartners 3ABD00043579 Rev C EN 2018 01 01 Contact us ...