56 Guidelines for planning the electrical installation
Selecting the supply disconnecting device
Install a hand-operated input disconnecting device between the AC power source and the
drive. The disconnecting device must be of a type that can be locked to the open position
for installation and maintenance work.
European Union
To agree with the European Union Directives, according to standard EN 60204-1,
Safety of
Machinery
, the disconnecting device must be one of the following types:
•
switch-disconnector of utilization category AC-23B (EN 60947-3)
•
disconnector that has an auxiliary contact that in all cases causes switching devices to
break the load circuit before the opening of the main contacts of the disconnector
(EN 60947-3)
•
circuit breaker suitable for isolation in accordance with EN 60947-2.
Other regions
The disconnecting device must conform to the applicable safety regulations.
Selecting the main contactor
If a main contactor is used, its utilization category (number of operations under load) must
be AC-1 according to IEC 60947-4,
Low-voltage switchgear and controlgear
. One main
contactor for the drive unit, or contactors for both basic modules can be used if they are
closed simultaneously. Select the contactor according to nominal voltage of the drive and
the drive or basic module current.
Examining the compatibility of the motor and drive
Use an asynchronous AC induction motor, permanent magnet motor, AC induction
servomotor or ABB synchronous reluctance motor (SynRM motor) with the drive. Several
induction motors can be connected at a time.
Select the motor size and drive type from the rating tables in chapter
basis of the AC line voltage and motor load. Use the DriveSize PC tool if you need to tune
the selection more in detail.
Make sure that the motor withstands the maximum peak voltage in the motor terminals,
see the
on page
. For basics of protecting the motor insulation and
bearings in drive systems, refer to section
Protecting the motor insulation and bearings
below.
Note:
•
Consult the motor manufacturer before you use a motor which nominal voltage differs
from the AC line voltage connected to the drive input.
•
The voltage peaks at the motor terminals are relative to the supply voltage of the drive,
not the drive output voltage.
•
If the motor and drive are not of the same size, consider the following operation limits
of the drive control program:
•
motor nominal voltage range 1/2 ... 2 ·
U
N
•
motor nominal current range 1/6 ... 2 ·
I
N
of the drive in DTC control and 0 ... 2 ·
I
N
in scalar control. The control mode is selected by a drive parameter.
Summary of Contents for ACS880-07XT Series
Page 1: ...ABB industrial drives Hardware manual ACS880 07XT drives 400 to 1200 kW ...
Page 4: ......
Page 12: ...12 ...
Page 20: ...20 Safety instructions ...
Page 26: ...26 Introduction to the manual ...
Page 54: ...54 Mechanical installation ...
Page 89: ...Electrical installation 89 PE 11 8 4 9 11 ...
Page 94: ...94 Electrical installation ...
Page 112: ...112 Fault tracing ...
Page 123: ...Maintenance 123 5 6 7 ...
Page 124: ...124 Maintenance 8 10 9 ...
Page 126: ...126 Maintenance 6 5 4 ...
Page 127: ...Maintenance 127 9 8 7 ...
Page 128: ...128 Maintenance 12 11 10 ...
Page 149: ...Dimensions 149 Dimension drawing examples Frame 2 R11 R10 with brake chopper ...
Page 150: ...150 Dimensions Frame 2 R11 R10 without brake chopper ...
Page 153: ...Dimensions 153 Location of input terminals ACS880 07XT 12 pulse ...
Page 154: ...154 Dimensions Location of output terminals ACS880 07XT R10 with du dt ...
Page 155: ...Dimensions 155 Location of output terminals ACS880 07XT R10 without du dt ...
Page 156: ...156 Dimensions Location of output terminals ACS880 07XT R11 with du dt ...
Page 157: ...Dimensions 157 Location of output terminals ACS880 07XT R11 without du dt ...
Page 158: ...158 Dimensions Location of PE terminals ACS880 07XT ...
Page 159: ...Dimensions 159 Location of resistor terminals ACS880 07XT R10 ...
Page 160: ...160 Dimensions Location of resistor terminals ACS880 07XT R11 ...
Page 168: ...www abb com drives www abb com drivespartners 3ABD00043579 Rev C EN 2018 01 01 Contact us ...