140 Technical data
Efficiency
96.0 … 98.0% at nominal power level depending on drive type
Protection classes
Degrees of protection
(IEC/EN 60529)
IP22 (standard), IP42 (optional),IP54(pending)
Overvoltage category
(IEC 60664-1)
III
Protective class
(IEC/EN 61800-5-1)
I
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated, indoor, controlled
environment.
Operation
installed for stationary
use
Storage
in the protective package
Transportation
in the protective package
Installation site altitude
0 to 2000 m above sea
level.
For attitude over 2000m,
contact ABB.
Output derated above
1000 m (3281 ft). See
section
drive modules with 50 Hz
and 60 Hz supply are
given below.
.
-
-
Air temperature
0 … +40 °C
(+32 … +104 °F). No
condensation allowed.
Output derated in the
range +40 … +50 °C
(+104 … +122 °F). See
.
-40 to +70 °C
(-40 to +158 °F)
-40 to +70 °C
(-40 to +158 °F)
Relative humidity
Max. 95%
Max. 95%
Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the
presence of corrosive gases.
Contamination
IEC/EN 60721-3-3:2002:
Classification of
environmental conditions
- Part 3-3: Classification
of groups of
environmental
parameters and their
severities - Stationary
use of weather protected
locations
IEC 60721-3-1:1997
IEC 60721-3-2:1997
Chemical gases
Class 3C2
Class 1C2
Class 2C2
Solid particles
Class 3S2. No
conductive dust allowed.
Class 1S3 (packing must
support this, otherwise
1S2)
Class 2S2
Summary of Contents for ACS880-07XT Series
Page 1: ...ABB industrial drives Hardware manual ACS880 07XT drives 400 to 1200 kW ...
Page 4: ......
Page 12: ...12 ...
Page 20: ...20 Safety instructions ...
Page 26: ...26 Introduction to the manual ...
Page 54: ...54 Mechanical installation ...
Page 89: ...Electrical installation 89 PE 11 8 4 9 11 ...
Page 94: ...94 Electrical installation ...
Page 112: ...112 Fault tracing ...
Page 123: ...Maintenance 123 5 6 7 ...
Page 124: ...124 Maintenance 8 10 9 ...
Page 126: ...126 Maintenance 6 5 4 ...
Page 127: ...Maintenance 127 9 8 7 ...
Page 128: ...128 Maintenance 12 11 10 ...
Page 149: ...Dimensions 149 Dimension drawing examples Frame 2 R11 R10 with brake chopper ...
Page 150: ...150 Dimensions Frame 2 R11 R10 without brake chopper ...
Page 153: ...Dimensions 153 Location of input terminals ACS880 07XT 12 pulse ...
Page 154: ...154 Dimensions Location of output terminals ACS880 07XT R10 with du dt ...
Page 155: ...Dimensions 155 Location of output terminals ACS880 07XT R10 without du dt ...
Page 156: ...156 Dimensions Location of output terminals ACS880 07XT R11 with du dt ...
Page 157: ...Dimensions 157 Location of output terminals ACS880 07XT R11 without du dt ...
Page 158: ...158 Dimensions Location of PE terminals ACS880 07XT ...
Page 159: ...Dimensions 159 Location of resistor terminals ACS880 07XT R10 ...
Page 160: ...160 Dimensions Location of resistor terminals ACS880 07XT R11 ...
Page 168: ...www abb com drives www abb com drivespartners 3ABD00043579 Rev C EN 2018 01 01 Contact us ...