200 Parameters
Scalar
Scalar control. This mode is suitable in special cases where
DTC cannot be applied. In scalar control, the drive is
controlled with a frequency reference. The outstanding motor
control accuracy of DTC cannot be achieved in scalar control.
Some standard features are disabled in scalar control mode.
Note:
Correct motor run requires that the magnetizing current
of the motor does not exceed 90% of the nominal current of
the inverter.
See also section
on page
.
1
99.06
Mot nom current
Defines the nominal motor current. Must be equal to the value
on the motor rating plate. If multiple motors are connected to
the drive, enter the total current of the motors.
Notes:
• Correct motor run requires that the magnetizing current of
the motor does not exceed 90% of the nominal current of
the drive.
• This parameter cannot be changed while the drive is
running.
0.0 … 6400.0 A
Nominal current of the motor. The allowable range is 1/6…2 ×
I
2N
of the drive (0…2 ×
I
2N
with scalar control mode).
10 = 1 A
99.07
Mot nom voltage
Defines the nominal motor voltage as fundamental phase-to-
phase rms voltage supplied to the motor at the nominal
operating point. This setting must match the value on the
rating plate of the motor.
Notes:
• With permanent magnet motors, the nominal voltage is the
BackEMF voltage at nominal speed of the motor. If the
voltage is given as voltage per rpm, e.g. 60 V per 1000
rpm, the voltage for a nominal speed of 3000 rpm is
3 × 60 V = 180 V. Note that the nominal voltage is not
equal to the equivalent DC motor voltage (EDCM)
specified by some motor manufacturers. The nominal
voltage can be calculated by dividing the EDCM voltage by
1.7 (or square root of 3).
• The stress on the motor insulation is always dependent on
the drive supply voltage. This also applies to the case
where the motor voltage rating is lower than that of the
drive and the supply.
• This parameter cannot be changed while the drive is
running.
1/6 … 2 ×
U
N
Nominal voltage of the motor.
10 = 1 V
99.08
Mot nom freq
Defines the nominal motor frequency.
Note:
This parameter cannot be changed while the drive is
running.
5.0 … 500.0 Hz
Nominal frequency of the motor.
10 = 1 V
99.09
Mot nom speed
Defines the nominal motor speed. The setting must match the
value on the rating plate of the motor.
Note:
This parameter cannot be changed while the drive is
running.
0 … 10000 rpm
Nominal speed of the motor.
1 = 1 rpm
No.
Name/Value
Description
FbEq