156 Parameters
34.14
Load high lim2
Maximum load (current or torque) at point 2 of user load
curve.
0 … 1600%
Maximum load at point 2.
1 = 1%
34.15
Load high lim3
Maximum load (current or torque) at point 3 of user load
curve.
0 … 1600%
Maximum load at point 3.
1 = 1%
34.16
Load high lim4
Maximum load (current or torque) at point 4 of user load
curve.
0 … 1600%
Maximum load at point 4.
1 = 1%
34.17
Load high lim5
Maximum load (current or torque) at point 5 of user load
curve.
0 … 1600%
Maximum load at point 5.
1 = 1%
34.18
Load integ time
Integration time used in limit supervision whenever enabled
by parameter
.
0 … 10000 s
Integration time.
1 = 1 s
34.19
Load cool time
Defines the cooling time. The output of the overload
integrator is set to zero if the load stays continuously below
the upper boundary of the user load curve.
0 … 10000 s
Load cooling time.
1 = 1 s
34.20
Underload time
Time for the underload function. See parameter
0 … 10000 s
Underload time.
1 = 1 s
35
35 Process variable
Selection and modification of process variables for display as
parameters
35.01
Signal1 param
Selects a signal to be provided as parameter
Speed rpm
(see page
1073742081
Speed %
(see page
1073742082
Frequency
(see page
1073742083
Current
(see page
).
1073742084
Current %
(see page
).
1073742085
Torque
(see page
).
1073742086
Dc-voltage
).
1073742087
Power inu
(see page
1073742102
Power motor
(see page
).
1073742103
SpRef unramp
(see page
).
1073742595
SpRef ramped
(see page
).
1073742597
SpRef used
(see page
).
1073742598
TorqRef used
1073742606
Process act
).
1073742851
Proc PID out
(see page
).
1073742853
Pointer
Value pointer setting (see
on page
).
-
No.
Name/Value
Description
FbEq