176 Parameters
44.14
Edge count2 func
Configures rising edge counter 2. The counter is incremented
every time the signal selected by parameter
switches on (unless a divisor value is applied –
see parameter
). After the limit set by
parameter
is reached, an alarm
specified by parameter
is given and
the counter is reset.
The current value of the counter is readable from parameter
. Bit 3 of
indicates
that the count has exceeded the limit.
44.15
Edge count2 src
Selects the signal to be monitored by rising edge counter 2.
See parameter
RO1
Relay output RO1 (as indicated by
, bit 0).
1073742338
Running
1073939969
Charged
1074333186
Const
). -
Pointer
44.16
Edge count2 lim
Sets the alarm limit for rising edge counter 1. See parameter
.
0 … 2147483647
Alarm limit for rising edge counter 2.
1 = 1
44.17
Edge count2 div
Divisor for rising edge counter 2. Determines how many rising
edges increment the counter by 1.
1 … 2147483647
Divisor for rising edge counter 2.
1 = 1
44.18
Edg cnt2 alm sel
Selects the alarm for rising edge counter 2. See parameter
.
Edge count2
Pre-selectable alarm for rising edge counter 2.
0
Main cntactr
Pre-selectable alarm for rising edge counter 2.
1
Output relay
Pre-selectable alarm for rising edge counter 2.
2
Motor starts
Pre-selectable alarm for rising edge counter 2.
3
Power ups
Pre-selectable alarm for rising edge counter 2.
4
Dc-charge
Pre-selectable alarm for rising edge counter 2.
5
No.
Name/Value
Description
FbEq
Bit
Function
0
Counter mode
0 = Loop: If alarm is enabled by bit 1, the alarm stays active only for 10 seconds.
1 = Saturate: If alarm is enabled by bit 1, the alarm stays active until reset.
1
Alarm ena (Alarm enable)
0 = Disable: No alarm is given when limit is reached.
1 = Enable: Alarm is given when limit is reached.