84 Parameters
Const
). -
Pointer
10.13
Em stop off3
Selects the source of the emergency stop OFF3 signal. The
drive is stopped along the emergency stop ramp time defined
by parameter
.
0 = OFF3 active.
Note:
This parameter cannot be changed while the drive is
running.
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
DI6
Digital input DI6 (as indicated by
, bit 5).
1074070017
DIO4
Digital input/output DIO4 (as indicated by
,
bit 3).
1073938947
DIO5
Digital input/output DIO5 (as indicated by
,
bit 4).
1074004483
DIO6
Digital input/output DIO6 (as indicated by
,
bit 5).
1074070019
Const
). -
Pointer
10.15
Em stop off1
Selects the source of the emergency stop OFF1 signal. The
drive is stopped using the active deceleration time.
Emergency stop can also be activated through fieldbus
(
).
0 = OFF1 active.
Note:
This parameter cannot be changed while the drive is
running.
DI1
Digital input DI1 (as indicated by
, bit 0).
1073742337
DI2
Digital input DI2 (as indicated by
, bit 1).
1073807873
DI3
Digital input DI3 (as indicated by
, bit 2).
1073873409
DI4
Digital input DI4 (as indicated by
, bit 3).
1073938945
DI5
Digital input DI5 (as indicated by
, bit 4).
1074004481
DI6
Digital input DI6 (as indicated by
, bit 5).
1074070017
DIO4
Digital input/output DIO4 (as indicated by
,
bit 3).
1073938947
DIO5
Digital input/output DIO5 (as indicated by
,
bit 4).
1074004483
DIO6
Digital input/output DIO6 (as indicated by
,
bit 5).
1074070019
Const
). -
Pointer
No.
Name/Value
Description
FbEq