150 Parameters
31.13
Mot nom tempRise
Defines the temperature rise of the motor when the motor is
loaded with nominal current. See the motor manufacturer's
recommendations.
The temperature rise value is used by the motor thermal
protection model when parameter
is set
0 … 300 °C
Temperature rise.
1 = 1 °C
31.14
Mot therm time
Defines the thermal time constant for the motor thermal
protection model (i.e. time inside which the temperature has
reached 63% of the nominal temperature). See the motor
manufacturer's recommendations.
The motor thermal protection model is used when parameter
.
100 … 10000 s
Motor thermal time constant.
1 = 1 s
No.
Name/Value
Description
FbEq
Motor nominal
temperature rise
Temperature
Time
Ambient temperature
100%
63%
100%
Time
Time
Motor thermal time
Motor load
Temperature rise