92 Parameters
13.14
AI3 max scale
Defines the real value that corresponds to the maximum
analogue input AI3 value defined by parameter
-32768.000 …
32768.000
Real value corresponding to maximum AI3 value.
1000 = 1
13.15
AI3 min scale
Defines the real value that corresponds to the minimum
analogue input AI3 value defined by parameter
. See the drawing at parameter
-32768.000 …
32768.000
Real value corresponding to minimum AI3 value.
1000 = 1
13.16
AI4 filt time
Defines the filter time constant for analogue input AI4. See
parameter
.
0.000 … 30.000 s
Filter time constant.
1000 = 1 s
13.17
AI4 max
Defines the maximum value for analogue input AI4. The input
type depends on the type and/or settings of the I/O extension
module installed. See the user documentation of the
extension module.
-22.000 … 22.000
mA or
-11.000 … 11.000 V
AI4 maximum value.
1000 = 1 unit
13.18
AI4 min
Defines the minimum value for analogue input AI4. The input
type depends on the type and/or settings of the I/O extension
module installed. See the user documentation of the
extension module.
-22.000 … 22.000
mA or
-11.000 … 11.000 V
AI4 minimum value.
1000 = 1 unit
No.
Name/Value
Description
FbEq
AI
(scaled)
AI
(mA/V)
Summary of Contents for ACS850 series