Fault tracing 235
0009
BC WIRING
(0x7111)
Brake resistor short circuit or
brake chopper control fault
Check brake chopper and brake resistor
connection.
Ensure brake resistor is not damaged.
0010
BC SHORT CIRCUIT
(0x7113)
Short circuit in brake chopper
IGBT
Replace brake chopper.
Ensure brake resistor is connected and
not damaged.
0011
BC OVERHEAT
(0x7181)
Brake chopper IGBT
temperature has exceeded
internal alarm limit.
Let chopper cool down.
Check resistor overload protection
function settings (parameters
Check that braking cycle meets allowed
limits.
Check that drive supply AC voltage is not
excessive.
0012
BR OVERHEAT
(0x7112)
Brake resistor temperature has
exceeded fault limit defined by
parameter
Stop drive. Let resistor cool down.
Check resistor overload protection
function settings (parameters
Check fault limit setting, parameter
.
Check that braking cycle meets allowed
limits.
0013
CURR MEAS GAIN
(0x3183)
Difference between output
phase U2 and W2 current
measurement gain is too great.
Contact your local ABB representative.
0014
CABLE CROSS CON
(0x3181)
Programmable fault:
Incorrect input power and
motor cable connection (i.e.
input power cable is connected
to drive motor connection).
Check input power connections.
0015
SUPPLY PHASE
(0x3130)
Programmable fault:
Intermediate circuit DC voltage
is oscillating due to missing
input power line phase or
blown fuse.
Check input power line fuses.
Check for input power supply imbalance.
0016
MOTOR PHASE
(0x3182)
Programmable fault:
Motor circuit fault due to
missing motor connection (all
three phases are not
connected).
Connect motor cable.
0017
ID-RUN FAULT
(0xFF84)
Motor ID Run is not completed
successfully.
Check motor settings (parameters
Check that no limits prevent ID run. The
following must apply:
For Reduced and Normal ID run:
–
> 55% of
< 0
– Supply voltage > 65% of
) > 100% (only for Normal ID
run).
Retry.
Code
Fault
(fieldbus code)
Cause
What to do