Parameters 73
06
06 Drive status
Drive status words.
06.01
Status word1
Status word 1 sent to the master.
-
No.
Name/Value
Description
FbEq
Bit
Name
Information
0
Ready
1 = Drive is ready to receive start command.
0 = Drive is not ready.
1
Enabled
1 = External run enable signal is received.
0 = No external run enable signal is received.
2
Started
1 = Drive has received start command.
0 = Drive has not received start command.
3
Running
1 = Drive is modulating.
0 = Drive is not modulating.
4
Em off
(off2)
1 = Emergency OFF2 is active.
0 = Emergency OFF2 is inactive.
5
Em stop
(off3)
1 = Emergency OFF3 (ramp stop) is active.
0 = Emergency OFF3 is inactive.
6
Ack startinh 1 = Start inhibit is active.
0 = Start inhibit is inactive.
7
Alarm
1 = Alarm is active. See chapter
.
0 = No alarm is active.
8
Ext2 act
1 = External control EXT2 is active.
0 = External control EXT1 is active.
9
Local fb
1 = Fieldbus local control is active.
0 = Fieldbus local control is inactive.
10
Fault
1 = Fault is active. See chapter
0 = No fault is active.
11
Local panel 1 = Local control is active, ie. drive is controlled from PC tool or control
panel.
0 = Local control is inactive.
12
Fault(-1)
1 = No fault is active.
0 = Fault is active. See chapter
13…31 Reserved